Texas REScheck Requirements (2026)
Key facts:
-
2015 IRC Ch. 11 — Statewide Minimum
-
Zones 2, 3 & 4
-
Major Cities: 2021 IECC or Later
-
Code Update In Active Rulemaking
Quick Answer: Texas commonly requires REScheck for: new single-family homes, additions/remodels affecting the thermal envelope, conditioned detached structures (workshops, guest houses, pool houses), barndominiums, and ADUs. REScheck is explicitly accepted statewide for the UA trade-off path — but because major cities enforce codes stricter than the state minimum, always confirm the local jurisdiction's code before selecting the code year.
Texas jurisdictions require REScheck and energy compliance documentation under the 2015 International Residential Code Chapter 11 — the statewide minimum energy code for single-family homes and duplexes, effective September 1, 2016 and still in force today. Texas is a home rule state with a unique two-tier structure: the State Energy Conservation Office (SECO) sets the statewide floor, and local jurisdictions enforce and may exceed it.
Major Texas cities have adopted stricter codes: Austin enforces the 2024 IECC with local amendments; Houston, Dallas, and San Antonio enforce the 2021 IECC with local amendments. Texas spans three IECC climate zones: Zone 2 (Hot-Humid, south/Gulf Coast), Zone 3 (Mixed, central Texas/DFW), and Zone 4 (Cold, Panhandle).
⚠ Texas Code Update In Active Rulemaking — Always Verify Your Jurisdiction: The statewide minimum remains the 2015 IRC Chapter 11 as of June 2026. SB 783, signed September 1, 2025, authorized SECO to proceed with rulemaking for a newer edition. SECO issued a public input request in November 2025 on adopting the 2024 IECC, with formal rulemaking expected by mid-2026. Never assume the statewide minimum applies — confirm the currently enforced code with the local permit office.
Texas's Two-Tier Energy Code Structure
SECO sets minimum statewide standards under Texas Health and Safety Code Chapter 388. All 1,200+ Texas cities, towns, and villages with building authority may adopt stricter codes. For nonattainment and affected counties, local amendments must be verified by the Energy Systems Laboratory (ESL) at Texas A&M.
-
Statewide minimum (single-family/duplex ≤ 3 stories): 2015 IRC Chapter 11 — effective September 1, 2016
-
Statewide minimum (commercial/multifamily): 2015 IECC
-
State-funded residential: 2015 IECC; federally-funded residential (committed after Nov 28, 2024): 2021 IECC
-
Local jurisdictions may adopt any code as stringent or stricter than the state minimum
-
SB 783 (signed Sept 1, 2025) enables SECO to proceed with rulemaking — formal adoption expected mid-2026
Common Permit Requirements
-
REScheck compliance report — accepted statewide for the UA trade-off path; match code year to the local jurisdiction
-
Manual J HVAC load calculations (ACCA Manual J or approved equivalent per N1103.7)
-
Manual S equipment selection documentation
-
Window and door schedule (U-factor and SHGC per NFRC, by climate zone)
-
Blower door test results — 5 ACH50 max for Zones 2/3; 3 ACH50 for Zone 4
-
Duct leakage test results — 4 CFM25 per 100 sq ft post-construction (required for all systems)
-
Permanent energy certificate posted at furnace/utility room
-
Cities on 2021 IECC: add mechanical ventilation documentation if blower door result is below 3 ACH50
When Is REScheck Required in Texas?
-
New single-family homes — every new one- and two-family home in a jurisdiction with an adopted energy code
-
Residential additions — new conditioned floor area must comply; existing structure isn't required to be brought into compliance
-
Major remodels affecting the thermal envelope — stripped-to-studs remodels, full window replacement, or new conditioned space
-
Conditioned detached structures — workshops, converted garages, pool houses, home gyms, guest cottages
Barndominiums, ADUs, and Emerging Project Types
Conditioned barndominiums are subject to the energy code regardless of steel-frame or post-frame construction. For Zone 2/3 projects, SHGC 0.25 is the most commonly missed spec on barndominiums with large roll-up door windows. Accessory dwelling units (backyard cottages, garage apartments, in-law suites) are treated as new residential construction in most jurisdictions — Austin's ADU-friendly zoning has made this a high-volume category under the 2024 IECC.
Major City Energy Codes in Texas
⚠ The Statewide Minimum Applies in Unincorporated Areas of Counties: Texas Health and Safety Code §388.004 is explicit — the adopted energy code applies not just within city limits but also in unincorporated county areas. A new home built outside city limits is still subject to the state minimum. County judges and commissioners courts enforce code there; verify enforcement capacity with the county.
Blower Door and Duct Requirements
Blower Door (Air Leakage Testing)
-
Zones 2 & 3 (statewide minimum): max 5 ACH50 — mandatory, no visual inspection alternative
-
Zone 4: max 3 ACH50 — mandatory
-
Cities on 2021 IECC (Austin, Houston, Dallas, San Antonio): max 3 ACH50 statewide, significantly stricter than state minimum
-
Testing per RESNET/ICC 380, ASTM E779, or ASTM E1827; written signed report required
-
Mechanical ventilation required when result falls below 5 ACH50 (2015 IRC) or below 3 ACH50 (2021 IECC)
-
Zone 2 prohibition: electric resistance heating can't be the primary system for new construction or full replacements
Duct Leakage Testing
-
Post-construction: max 4 CFM25 per 100 sq ft — mandatory regardless of duct location (unlike most states, tested even when ducts are inside conditioned space)
-
Rough-in: max 4 CFM25/100 sq ft with air handler; 3 CFM25 without
-
Supply ducts in unconditioned attics: min R-8; other supply/return ducts outside conditioned space: min R-6
-
Framing cavities may NOT be used as supply or return ducts; duct sealing requires mastic or equivalent (duct tape alone unacceptable)
Common REScheck Failure Reasons in Texas
Envelope Errors by Zone
-
Wrong climate zone — placing a DFW project in Zone 2 instead of Zone 3; Dallas County is Zone 3, Houston is Zone 2
-
Zone 2 wall insulation — state minimum allows R-13 cavity-only, but Austin/Houston/San Antonio's 2021 IECC requires R-20 or R-13+5ci
-
Zone 4 ceiling requirement — Amarillo/Lubbock need R-49, not Zone 3's R-38
-
SHGC non-compliance — 0.25 applies to Zones 2/3 and can't be traded off; large window packages on custom homes frequently exceed it, especially in Houston and Austin
-
Wrong code year selected in REScheck — using statewide 2015 IRC Ch. 11 for an Austin (2024 IECC) or Houston (2021 IECC) project
Mechanical and Field Issues
-
Blower door failures from top plate/recessed lighting/boot/plumbing chase leaks, even at the lenient 5 ACH50 threshold
-
Duct leakage failures in attic systems — 150°F+ attic temps degrade duct tape rapidly; mastic sealing is critical
-
Duct testing documentation missing — Texas requires it even for conditioned-space ducts
-
Electric resistance heat used as primary system in Zone 2 — violates code; heat pumps or gas required
-
Energy certificate omitted at furnace/utility room — frequently overlooked final inspection item
-
Manual J documentation missing — oversized systems without load calc are a frequent correction
Frequently Asked Questions
What energy code does Texas currently use for residential construction?
The statewide minimum is the 2015 IRC Chapter 11, effective September 1, 2016, adopted by SECO. This remains current as of June 2026. Austin enforces the 2024 IECC; Houston, Dallas, and San Antonio enforce the 2021 IECC. SB 783 (Sept 1, 2025) authorized SECO to begin rulemaking toward a newer edition, expected by mid-2026. Always verify with the local permit office.
What climate zones does Texas have?
Three: Zone 2 (Hot-Humid — Houston, San Antonio, Austin, Corpus Christi, McAllen, Laredo, Brownsville), Zone 3 (Mixed — Dallas, Fort Worth, Waco, Tyler, Midland, Abilene), Zone 4 (Cold — Amarillo, Lubbock, Wichita Falls). Zone is determined by county and is the single most important input for a Texas REScheck.
Is blower door testing required in Texas?
Yes, mandatory statewide. Under the state minimum: 5 ACH50 for Zones 2/3, 3 ACH50 for Zone 4. Cities on the 2021 IECC (Austin, Houston, Dallas, San Antonio) require 3 ACH50 for all zones. There is no visual inspection alternative in Texas.
Do I need a REScheck for a barndominium in Texas?
Yes, if conditioned and the local jurisdiction has adopted an energy code — regardless of steel-frame, post-frame, or stick-built construction. SHGC 0.25 in Zones 2/3 is especially important on barndominiums with large roll-up door windows.
Do I need a REScheck for an ADU in Texas?
Yes, in most jurisdictions — ADUs are generally treated as new residential construction. Austin applies the 2024 IECC to ADUs; Houston, San Antonio, and Dallas apply the 2021 IECC. Smaller cities and unincorporated areas use the statewide 2015 IRC minimum.
What SHGC is required in Texas?
0.25 maximum in Zones 2 and 3 (the vast majority of the state, including all major cities) — mandatory, cannot be traded off. 0.40 maximum in Zone 4 (Amarillo, Lubbock, Panhandle).
What does the Texas HERS/ERI path require?
Available statewide under Health & Safety Code §388.003. Max ERI (as of Sept 1, 2022) is 59 for Zones 2/3, 63 for Zone 4 — stepped down from 65 (2016) to 63 (2019). Certified HERS Rater required. Texas does not require an R408 additional efficiency package on the ERI path. Zone 2 still can't use electric resistance heat as the primary system.
When will Texas update its statewide energy code?
In active rulemaking. SB 783 (Sept 1, 2025) resolved conflicting statutes that had blocked SECO from updating. A public input request on the 2024 IECC went out in November 2025; a draft rule is expected by mid-2026. Until formally adopted and published in the Texas Register, the 2015 IRC Chapter 11 remains the statewide minimum.
Does the Texas energy code apply outside city limits?
Yes. Health & Safety Code §388.004 applies the adopted energy code in unincorporated county areas as well as cities. County judges and commissioners courts enforce it, though enforcement capacity varies — verify with the county.